AISB · Verified CRE Claims Library
Verified CRE Claims: Energy & M&V
This library is an informational reference, not engineering or legal advice. Confirm the current edition of any cited standard with the issuing body before relying on it for design, compliance, or investment decisions.
HVAC, controls, energy engineering, and IPMVP measurement & verification standards.
8 verified claims · back to the library hub
ASHRAE Guideline 14-2014 declares a whole-building energy model calibrated to monthly data if the absolute NMBE is less than 5% and CV(RMSE) is less than 15%, a materially tighter tolerance than the hourly criteria.
ASHRAE 62.1-2022 §6.2.2.1 prescribes minimum outdoor air ventilation rates for office space at 5 cfm/person plus 0.06 cfm/sqft
ASHRAE Guideline 14-2014 declares a whole-building energy model calibrated to hourly data if the Normalized Mean Bias Error (NMBE) is within ±10% and the Coefficient of Variation of the Root Mean Square Error, CV(RMSE), is within ±30%.
GB 55015-2021 requires an average building energy-savings rate of 75% for residential buildings in severe cold climate zones, 65% for residential buildings in other climate zones, and 72% for public buildings, relative to the pre-reform-era (1980s) baseline used in the Chinese building energy-code system.
ASHRAE 62.1-2022 §6.2.6.1 mandates demand-controlled ventilation (DCV) for spaces with design population density > 25 persons per 1000 sqft when occupiable space exceeds 500 sqft
GB 55015-2021 sets the average design energy-consumption reduction target for new residential and public buildings at 30% below the level required by the energy-efficiency design standards implemented in 2016 ("在2016年执行的节能设计标准基础上降低30%").
PIPL Article 66 authorizes provincial-or-higher-level cyberspace/enforcement authorities to fine a personal-information processor, for grave (serious) violations, up to RMB 50 million or up to 5% of the processor's preceding year's annual turnover (whichever is applicable/higher per the enforcement authority's determination), in addition to ordering suspension of the relevant business or of all operations for rectification and notifying competent authorities to revoke business permits or license
ASHRAE 90.1-2022 §6.5.1 (Table 6.5.1) requires air economizers for cooling systems with capacity ≥ 54,000 Btu/h in all climate zones except 1A and 1B